
ISA-44-2-OD ENMET Corporation
9
3.3 Sensor Hook-up
The oxygen cell comes packaged in a sealed vapor proof bag. The cell needs to be installed in the remote sensor
enclosure after the enclosure has been mounted. See Figure 6. This procedure is the same as the procedure described
in Section 5.3
The MOS sensor is connected to the ISA-44-2-OD control unit with three conductor wiring, use the correct oiltight
fitting. Two conductors supply heater current to the sensor. The third conductor is a signal wire. Size of heater wire
depends on the distance between the particular sensor and the control unit. See Table 4.
Sensor wires correspond to the normal wire code:
orange – heater
brown – heater ground
blue – signal
Figure 7: Internal View of Sensor Wiring
NOTE: The three color-coded wiring attachments must be performed by the user when replacing the sensor.
Table 4: Recommended Wire Gauge
Distance from Sensor to Control Unit Recommended Wire Gauge
250 feet 16 AWG
350 feet 14 AWG
Longer Distances Contact Factory
CAUTION: After you mount and install the ISA – 44-2-OD, you must adjust the sensor heater voltage (see Section 3.4).
This equipment is usually permanently installed, with sensor, power, and relay wires run through hard conduit. The
enclosure is not punched, so wiring may approach the enclosure from any direction; however, the bottom of the
enclosure is the best wiring entrance surface.
1. The OPERATE switch should be in the HORN OFF position.
2. Insert each set of sensor wires through a conduit; install with a watertight fitting and tighten the fitting by hand.
Be sure to leave enough wire inside the enclosure for easy hook-up to terminals. The location of terminals
corresponding to each sensor is shown in Figure 3, 4 and 7.
Sensor Wiring
FOR 812 / 813 / 814 SENSORS
Position Function Wire Color
1 Signal (Blue)
2 Heater (Orange)
3 Ground (Brown)
Optional
Splash Shield
Sensor Wiring
Terminal
Comentários a estes Manuais